Current through Register No. 50, December 12, 2024
Section Puc 2506.03 - Metering of Co-Fired Electric Generating Sources(b) For co-fired sources, the source shall calculate the portion of electricity generated from the combustion of Class I biomass fuels quarterly based on the heat input of the facility by measuring the energy content of each combusted fuel using the low heat value as combusted, the mass or volumetric input flow of each of the fuels combusted, and the total electricity produced.(c) For any Class I biomass fuel, the initial energy content shall be based on the average of a minimum of 5 samples of that fuel taken over the course of the initial quarter, or on the fuel supply contract for that fuel delivered in the initial quarter.(d) If all the values for the energy content from the samples are within 5 percent of the average value of the samples, on a dry basis, then beginning with the subsequent quarter, the co-fired source may use a value for energy content from annual sampling of the Class I biomass fuel.N.H. Admin. Code § Puc 2506.03
Derived from Volume XXXV Number 01, Filed January 8, 2015, Proposed by #10741, Effective 12/5/2014.Amended by Volume XXXVIII Number 06, Filed February 8, 2018, Proposed by #12473, Effective 2/1/2018, Expires 2/1/2028.