N.H. Admin. Code § He-P 824.07

Current through Register No. 50, December 12, 2024
Section He-P 824.07 - HH Construction, Modifications or Renovations
(a) For new construction and for rehabilitation of an existing building, including, but not limited to, renovations, modifications, reconstruction, and additions, construction documents and shop drawings, including stamped architectural, sprinkler, and fire alarm plans, shall be submitted to the department at least 60 days prior to the start of such work.
(b) The architectural, sprinkler, and fire alarm plans in (a) above shall accurately show the room designation(s) and exact measurements of each area to be licensed, including but not limited to window and door sizes and each room's use.
(c) Architectural, sprinkler, and fire alarm plans shall be submitted to the state fire marshal's office as required by RSA 153:10-b, V.
(d) Any licensee or applicant who wants to use performance-based design to meet the fire safety requirements shall provide the department with documentation of fire marshal approval for such methods.
(e) The department shall review construction documents, drawings, and plans of a newly proposed or existing facility for compliance with all applicable sections of RSA 151 and He-P 824 and shall notify the applicant or licensee as to whether the proposal complies with these requirements.
(f) The HH shall comply with all applicable state laws, rules, and local ordinances when undertaking construction or rehabilitation.
(g) A licensee or applicant undertaking construction, repairs, renovations, rehabilitation or modifications of a building shall comply with the appropriate chapters and sections of the state fire code and state building code.
(h) All HHs newly constructed or rehabilitated after the 2022 effective date of these rules shall comply with the Facility Guidelines Institutes (FGI) "Guidelines for Design and Construction of Residential Health, Care, and Support Facilities" (2022 edition), as applicable, available as noted in Appendix A.
(i) Where rehabilitation is done within an existing facility, all such work shall comply with applicable sections of the FGI "Guidelines for Design and Construction of Residential Health, Care, and Support Facilities" (2022 edition), available as noted in Appendix A.
(j) The department shall be the authority having jurisdiction for the requirements in He-P 824.07(h)-(i) and shall negotiate compliance with the licensee and their representatives and grant waivers in accordance with He-P 824.10 as appropriate.
(k) Penetrations, holes, or other openings in fire walls, fire partitions, smoke barriers, floors, and ceilings that allow the transfer of fire, heat, or smoke shall be closed and sealed using a listed or approved fire system that provides an equivalent rating as provided by the original surface.
(l) Waivers granted by the department for construction or rehabilitation under the FGI guidelines above shall not require annual renewal unless the underlying reason or circumstances for the waivers change.
(m) Exceptions or variances pertaining to the state fire code referenced in He-P 824.07(g) shall be granted only by the state fire marshal.
(n) Exceptions or variances pertaining to the state building code shall be granted by the local building official or the state fire marshal if in a state owned building.
(o) The building, including all construction and rehabilitated spaces, shall be inspected pursuant to He-P 824.09 prior to its use.

N.H. Admin. Code § He-P 824.07

#5648, eff 6-25-93; ss by #7020, INTERIM, eff 6-23-99, EXPIRED: 10-21-99

New. #9317, eff 11-8-08

Amended by Volume XXXVII Number 19, Filed May 11, 2017, Proposed by #12169, Effective 4/29/2017, Expires 10/26/2017.
Amended by Number 15, Filed April 13, 2023, Proposed by #13572, Effective 3/1/2023, Expires 3/1/2033.