N.H. Admin. Code § He-P 804.07

Current through Register No. 50, December 12, 2024
Section He-P 804.07 - ALR-RC New Construction and Existing Rehabilitation
(a) For new construction and for rehabilitation of an existing building, including, but not limited to, certain repairs, renovations, modifications, reconstruction, and additions, construction documents and shop drawings, including architectural, sprinkler, and fire alarm plans shall be submitted to the department 60 days prior to the start of such work.
(b) The architectural, sprinkler, and fire alarm plans in (a) above shall accurately show the room designation(s) and exact measurements of each area to be licensed, including but not limited to window and door sizes and each room's use.
(c) Architectural, sprinkler, and fire alarm plans shall be submitted to the state fire marshal's office as required by RSA 153:10-b, V.
(d) Any licensee or applicant who wants to use performance-based design to meet the fire safety requirements shall provide the department with documentation of fire marshal approval for such methods.
(e) The department shall review construction documents, drawings, and plans of a newly proposed or existing facility for compliance with all applicable sections of RSA 151 and He-P 804 and shall notify the applicant or licensee as to whether the proposal complies with these requirements.
(f) Construction and rehabilitation initiated prior to receiving department approval shall be done at the applicant or licensee's own risk.
(g) The ALR-RC shall comply with all applicable state laws, rules, and local ordinances when undertaking construction or rehabilitation.
(h) A licensee or applicant undertaking construction or rehabilitation of a building shall comply with the following:
(1) The state fire code, Saf-C-6000, including but not limited to at a minimum:
a. For 3 residents or fewer, the One and Two Family Dwelling chapter of the life safety code; and
b. For 4 residents or more, the Residential Board and Care Occupancy chapter of the life safety code; and
(2) The state building code as defined in RSA 155-A:1, IV, as amended by the building code review board pursuant to RSA 155-A:10, V; and
(i) All ALR-RCs newly constructed or rehabilitated after the 2017 effective date of these rules shall comply with the Facility Guidelines Institutes (FGI) "Guidelines for Design and Construction of Residential Health, Care, and Support Facilities," Residential Healthcare chapter, 2014 edition, as applicable, available as noted in Appendix A.
(j) Where rehabilitation is done within an existing facility, all such work shall comply, insofar as practicable, with applicable sections of the FGI "Guidelines for Design and Construction of Residential Health, Care, and Support Facilities," Residential Healthcare chapter, 2014 edition, available as noted in Appendix A.
(k) Per the FGI "Guidelines for Design and Construction of Residential Health, Care, and Support Facilities," Residential Healthcare chapter, 2014 edition, available as noted in Appendix A, and notwithstanding (j) above, where it is evident that a reasonable degree of safety is provided, the requirements for existing buildings shall be permitted to be modified if their application would be impractical in the judgment of the authority having jurisdiction.
(l) The department's bureau of health facilities administration shall be the authority having jurisdiction for the requirements in (i) -(k) above and shall negotiate compliance and grant waivers in accordance with He-P 804.10 as appropriate.
(m) Penetrations, holes, or other openings in fire walls, fire partitions, smoke barriers, floors, and ceilings that allow the transfer of fire, heat, or smoke shall be closed and sealed using a listed or approved sealant that provides an equivalent rating as provided by the original surface.
(n) Waivers granted by the department for construction or rehabilitation under the FGI guidelines above shall not require annual renewal unless the underlying reason or circumstances for the waivers change.
(o) Exceptions or variances pertaining to the state fire code referenced in (h) (1) above shall be granted only by the state fire marshal.
(p) The building, including all construction and rehabilitated spaces, shall be subject to an inspection pursuant to He-P 804.09 prior to its use.

N.H. Admin. Code § He-P 804.07

#2261, eff 1-17-83; ss by #3193, eff 1-28-86; rpld by #4516, eff 10-28-88; ss by #5317, EMERGENCY, eff 1-29-92, EXPIRED: 5-28-92

New. #5511, eff 11-25-92; amd by #5665, eff 7-14-93; ss by #6895, INTERIM, eff 11-26-98, EXPIRED: 3-26-99

New. #9121, eff 4-3-08

Amended by Volume XXXVI Number 49, Filed December 8, 2016, Proposed by #12047, Effective 11/19/2016, Expires 5/18/2017.
Amended by Volume XXXVII Number 45, Filed November 09, 2017, Proposed by #12414, Effective 11/3/2017, Expires 11/3/2027.