N.H. Admin. Code § He-P 2102.07

Current through Register No. 50, December 12, 2024
Section He-P 2102.07 - Analysis Results
(a) Sample analysis results shall be maintained at the plant for at least 2 years.
(b) The plant ownership shall make all analysis results available for review by the commissioner or an agent of the commissioner.
(c) Whenever any sampling result indicates that a water sample contains contaminants above the quality standards set forth in He-P 2102.02 or a bottler has reason to believe that a substance might be present in a water source or finished product that might cause a product to be a reportable food, as defined in 21 USC 350f.417(a) (2), the person responsible for the bottling plant shall:
(1) File an oral report with the department within 24 hours; and
(2) File a written report to the department within 3 days that explains the contamination levels and what action was taken by the ownership because of the contaminant level.
(d) When a water sample result does not meet the quality standard as set forth in He-P 2102.02, bottling plant personnel shall conduct additional testing as follows:
(1) For microbiological samples test results which show coliform bacteria in the water, samples shall be tested at least 2 times each week on non-consecutive days for one month following the original sample and after any corrective actions have been taken;
(2) For chemical, physical and radiological contaminants, samples shall be tested at least once each month for 3 months following the original sample and after any corrective actions have been taken; and
(3) The plant or bulk source ownership shall submit results of all follow-up tests to the department.

N.H. Admin. Code § He-P 2102.07

Derived From Volume XXXVIII Number 50, Filed December 13, 2018, Proposed by #12680, Effective 11/27/2018, Expires 11/27/2028.