Current through Register No. 50, December 12, 2024
Section Env-Ws 372.11 - Acceptable Sources of Water Supply(a) The use of surface water shall not be allowed for any small communitywatersystem.(b) A minimum of 2 wells shall be required for the following systems: (1) A community water system where the design flow exceeds 13,500 gpd; and(2) Any NTNC water system whose reliability is directly important to the public health as specified in Env-Ws 372.02(g) and where the residential-equivalent units exceeds 30.(c) If connection to a municipal water system is proposed, the applicant shall submit to the department a letter of confirmation from the supplying water system owner.(d) The letter of confirmationshall state that:(1) Adequate quantities of water are available to serve the proposed water system; and(2) With the proposed water system on-line, adequate system pressures will be maintained.(e) Design criteria for municipal water system piping extensions shall be as specified in Env-Ws 374 .N.H. Admin. Code § Env-Ws 372.11
(See Revision Note at chapter heading Env-Ws 300) #6521, eff 6-4-97; ss by #8360, INTERIM, eff 6-4-05, EXPIRES: 12-1-05; ss by #8496, eff 11-30-05