N.H. Admin. Code § Env-Ws 364.08

Current through Register No. 45, November 7, 2024
Section Env-Ws 364.08 - Approved Backflow Prevention Devices
(a) Only approved backflow prevention devices shall be used.
(b) Only the types of backflow prevention devices listed in Table 364-1 below shall be used for the containment of on-premise hazards for low and high degree of hazard situations respectively:

Table 364-1

Acceptable Backflow Prevention Devices for Degrees of Hazards

Low Degree of Hazard High Degree of Hazard
Air gap Air gap
Pressure vacuum breaker Reduced pressure backflow device
Double check valve assembly A combination of the above
Reduced pressure backflow device
A combination of the above

(d) A backflow prevention device shall not be installed in a location where it will:
(1) Be subject to corrosive fumes, grit, or sticky or abrasive liquids;
(2) Be subject to flooding or mechanical abuse;
(3) Not be easily accessible for testing and repair;
(4) Be in a pit or built into or close to walls or other obstructions; or
(5) Be in a vertical position unless the backflow prevention device was certified for that orientation.

N.H. Admin. Code § Env-Ws 364.08

#6521, eff 6-4-97 (See Revision Note at chapter heading for Env-Ws 300); ss by #8360, INTERIM, eff 6-4-05, EXPIRES: 12 -1-05; ss by #8476, eff 11-30-05