N.H. Admin. Code § Env-Ws 364.06

Current through Register No. 50, December 12, 2024
Section Env-Ws 364.06 - Cross-Connection Permits
(a) The supplier shall not allow cross-connections within the public water system unless deemed necessary due to:
(1) Inadequate fire protection capability of the public system; or
(2) High process water needs.
(b) The owner of any premises where a cross-connection exists shall apply for a cross-connection permit on the forms provided by the supplier.
(c) All permits shall be:
(1) Issued by the supplier for a term not to exceed 5 years; and
(2) Subject to revocation by the supplier.
(d) Each permit shall identify:
(1) The owner's name, mailing address, and daytime telephone number;
(2) The location of the backflow prevention device;
(3) The name of the manufacturer of the backflow prevention device;
(4) The size and model number of the backflow prevention device;
(5) A description of contaminants that could be introduced through the cross-connection;
(6) The frequency of inspections and testing of the backflow prevention device; and
(7) The permit number.
(e) The holder of a cross-connection permit shall apply for the permit to be renewed every 5 years or:
(1) Whenever a change has occurred in the existing degree of hazard classification; or
(2) A change has been made in the type of backflow prevention device installed.
(f) Cross-connection permits shall be non-transferable.

N.H. Admin. Code § Env-Ws 364.06

(See Revision Note at chapter heading for Env-Ws 300) #6521, eff 6-4-97; ss by #8360, INTERIM, eff 6-4-05, EXPIRES: 12 -1-05 ; ss by #8476, eff 11-30-05