N.H. Admin. Code § Env-Wq 1109.08

Current through Register No. 50, December 12, 2024
Section Env-Wq 1109.08 - Disinfection Methods
(a) Each component of a primary disinfection system shall comply with Env-Wq 1108.22(a)(1).
(b) A PBF shall use at least one of the following primary disinfection methods in order to meet the water quality standards specified in Env-Wq 1108.12 and Env-Wq 1108.13 for each PBF:
(1) A positive displacement pump type disinfection unit providing hypochlorination;
(2) A disinfection unit that controls the rate of hypochlorite or bromine tablet erosion; or
(3) A salt electrolytic chlorine generator.
(c) A disinfection unit as specified in (b)(1) or (2), above, shall be capable of feeding at a rate to permit a free residual chlorine concentration of 10 mg/L or a free residual bromine concentration of 22.5 mg/L to be maintained in the pool.
(d) A salt electrolytic chlorine generator (ECG) as specified in (b)(3), above, shall:
(1) Have a total dissolved solids (TDS) readout, a low salt indicator, and integrated pH monitoring and management;
(2) Have a feed rate that is adjustable from zero to full range;
(3) Be capable of providing a chlorine dosage equivalent to 100% of the total daily requirement during peak bather load;
(4) Be installed according to manufacturer's instructions; and
(5) Maintain the saline content of the pool or spa water in the required range specified by the manufacturer.
(e) Gaseous chlorine shall not be used as a disinfection method.
(f) Stabilized chlorine or bromine shall not be used as a disinfection method for indoor facilities.
(g) Each disinfection unit and ECG shall be:
(1) Installed in accordance with the manufacturer's instructions; and
(2) Wired such that the chemical feed equipment cannot operate when circulation flow stops.

N.H. Admin. Code § Env-Wq 1109.08

Derived from Volume XLI Number 19, Filed May 13, 2021, Proposed by #13198, Effective 5/1/2021, Expires 5/1/2031 (see Revision Note #3 at chapter heading for Env-Wq 1100) (formerly Env-Wq 1106.08)