N.H. Admin. Code § Env-Or 406.22

Current through Register No. 45, November 7, 2024
Section Env-Or 406.22 - Hydrostatic Tightness Test
(a) If a hydrostatic tightness test is performed pursuant to Env-Or 406.11(d)(3), the test shall be conducted:
(1) After all seams and fittings have been completed and all piping and conduits have been installed;
(2) At a level that is within one inch of the top of the sump;
(3) By recording the liquid level measurements at the beginning and end of the test;
(4) For a minimum of 3 hours; and
(5) With no addition of liquid to the sump.
(b) A passing hydrostatic test, when conducted in accordance with (a), above, shall have no loss of liquid or observed leaks after the complete duration of the test.

N.H. Admin. Code § Env-Or 406.22

(See Revision Note at chapter heading for Env-Or 400) #10393, eff 9-1-13

The amended version of this section by New Hampshire Register Volume 38, Number 45, eff. 10/10/2018 is not yet available.