N.H. Admin. Code § Env-Or 406.10

Current through Register No. 45, November 7, 2024
Section Env-Or 406.10 - Cathodic Protection System Testing
(a) The owner shall test:
(1) Sacrificial anode systems within 6 months of installation and every 3 years thereafter; and
(2) Impressed current systems within 6 months of installation and every 3 years thereafter.
(b) The individual conducting the testing shall be a cathodic protection tester.
(c) The owner shall submit the following information in a report of the cathodic protection test generated by the owner, on a form made available by the department, or any other document:
(1) The information required by Env-Or 406.07(c)(1)-(6);
(2) A description of the equipment used to conduct the test;
(3) Test locations;
(4) Test results;
(5) For impressed current systems, the specified rectifier DC output range in volts and amps; and
(6) The tester's International Code Council, Steel Tank Institute, or NACE certification number.
(d) The cathodic protection tester who has conducted the test shall sign the test report in accordance with Env-Or 406.07(e).
(e) When a cathodic protection test is performed, the owner shall send the test report to the department no later than 30 days after the date of the test.

N.H. Admin. Code § Env-Or 406.10

(See Revision Note at chapter heading for Env-Or 400) #10393, eff 9-1-13

Amended by Volume XXXVIII Number 45, Filed November 8, 2018, Proposed by #12643, Effective 10/10/2018, Expires 10/10/2028.