N.H. Admin. Code § Env-Or 306.01

Current through Register No. 50, December 12, 2024
Section Env-Or 306.01 - Operation and On-going Maintenance
(a) No person shall operate an AST system that does not have secondary containment in compliance with Env-Or 305.07.
(b) Secondary containment and lining materials shall be maintained to meet permeability requirements for the operational life of the AST system.
(c) If gravity drain pipes are used in secondary containment, all valves shall be locked in a closed position except when a controlled discharge of stormwater is being conducted.
(d) No person shall operate an oil transfer pump unless it has been installed as required by Env-Or 305.10.
(e) All tanks and connected piping shall be maintained so as to prevent leaks or seeps.
(f) The markings required by Env-Or 305.03 shall be maintained so as to be readily discernable from the distance at which the lettering will typically be viewed.
(g) The paint or other coating required by Env-Or 305.06(c) shall be maintained so as to prevent corrosion of the underlying metal.
(h) The concrete pad or impermeable surface required by Env-Or 305.13(c) for oil transfer and dispensing areas and the positive limiting barriers required by Env-Or 305.13(d)(2) shall be maintained so as to prevent any contained oil from escaping to the environment.

N.H. Admin. Code § Env-Or 306.01

(See Revision Note at chapter heading for Env-Or 300) #10487, eff 2-7-14