Table 714-1: Summary of Monitoring Requirements for Water Quality Parameters
Monitoring period; Location | Parameters | Frequency |
Initial water quality monitoring: | ||
- Taps - Entry point(s) to distribution system | - pH - alkalinity - conductivity - water temperature - calcium A - orthophosphate B - silica C | As specified in 40 CFR § 141.87, except that the frequency shall be twice in 90 days after the date of action level exceedance |
Routine water quality monitoring: | ||
- Taps | - pH - alkalinity - calcium A - orthophosphate B - silica C | As specified in 40 CFR § 141.87, except that the frequency shall be every 3 months for parameters to be reported twice during each monitoring period |
- Entry point(s) to distribution system | - pH - alkalinity D - inhibitor E | No less frequently than every 2 weeksF |
Optimal water quality parameters: | ||
- Taps | - pH - alkalinity - calcium A orthophosphate B - silica C | Every 6 months |
- Entry points(s) to distribution system | - pH - alkalinityD - inhibitor E | No less frequently than every 2 weeks F |
Reduced water quality monitoring: | ||
- Taps | - pH - alkalinity - calcium A - orthophosphate B - silica C | Every 6 months, annually or every 3 years; reduced number of sites |
- Entry point(s) to distribution system | - pH - alkalinityD - inhibitor E | No reductions; continues no less frequently than every 2 weeks F |
N.H. Admin. Code § Env-Dw 714.09
#9859, eff 2-8-11 (See Revision Note #4 at chapter heading for Env-Dw 700)