N.H. Admin. Code § Env-Dw 505.08

Current through Register No. 50, December 12, 2024
Section Env-Dw 505.08 - Approved Backflow Prevention Devices
(a) Only approved backflow prevention devices shall be used.
(b) Only the types of backflow prevention devices listed in Table 505-1 below shall be used for the containment of on-premise hazards for low and high degree of hazard situations respectively:

Table 505-1

Acceptable Backflow Prevention Devices for Degrees of Hazards

Low Degree of HazardHigh Degree of Hazard
Air gap Air gap
Pressure vacuum breaker Reduced pressure backflow device
Double check valve assembly A combination of the above
Reduced pressure backflow device
A combination of the above

(c) A backflow prevention device shall not be installed in a location where it will:
(1) Be subject to corrosive fumes, grit, or sticky or abrasive liquids;
(2) Be subject to flooding or mechanical abuse;
(3) Not be easily accessible for testing and repair;
(4) Be in a pit or built into or close to walls or other obstructions; or
(5) Be in a vertical position unless the backflow prevention device was certified for that orientation.

N.H. Admin. Code § Env-Dw 505.08

(See Revision Note at part heading for Env-Dw 505) #10615, eff 6-1-14