Section Env-A 3510.02 - Small, Remote HMIWI Inspection Coverage

Inspections pursuant to Env-A 3510.01 shall include the following:

(a) Inspection of all burners, pilot assemblies, and pilot sensing devices for proper operation;
(b) Proper adjustment of primary and secondary chamber combustion air flow;
(c) Inspection of hinges and door latches;
(d) Inspection of dampers, fans, and blowers for proper operation;
(e) Inspection of HMIWI door and door gaskets for proper sealing;
(f) Inspection of motors for proper operation;
(g) Inspection of primary chamber refractory lining;
(h) Inspection of incinerator shell for corrosion and hot spots;
(i) Inspection of secondary/tertiary chamber and stack;
(j) Inspection of mechanical loader, including limit switches, for proper operation, if applicable;
(k) Visual inspection of waste bed grates;
(l) For the burn cycle that follows the inspection, documentation that the incinerator is operating properly and that any necessary adjustments have been made;
(m) Inspection of air pollution control device or devices for proper operation, if applicable;
(n) Inspection of waste heat boiler systems to ensure proper operation, if applicable;
(o) Inspection of bypass stack components;
(p) Proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and
(q) General observation that the equipment is maintained in good operating condition.