TABLE 3500-1: EMISSION LIMITS FOR SMALL, REMOTE HMIWI
Pollutant | HMIWI Emission Limits |
Particulate matter | 197 milligrams per dry standard cubic meter, or 0.086 grains per dry standard cubic foot |
Carbon monoxide | 40 parts per million by volume |
Dioxins/furans | If measured as total dioxins/furans, either: 800 nanograms per dry standard cubic meter total dioxins/furans; or 350 grains per billion dry standard cubic feet total dioxins/furans. If measured as toxic equivalency (TEQ), either: 15 nanograms per dry standard cubic meter TEQ; or 6.6 grains per billion dry standard cubic feet TEQ. |
Hydrogen chloride | 3100 parts per million by volume |
Sulfur dioxide | 55 parts per million by volume |
Nitrogen oxides | 250 parts per million by volume |
Lead | 10 milligrams per dry standard cubic meter; or 4.4 grains per thousand dry standard cubic feet |
Cadmium | 4 milligrams per dry standard cubic meter; or 1.7 grains per thousand dry standard cubic feet |
Mercury | 0.055 milligrams per dry standard cubic meter; or 0.024 grains per thousand dry standard cubic feet |
N.H. Admin. Code § Env-A 3505.01
#6938, eff 1-30-99; amd by #7127, eff 10-30-99; ss by #8788, eff 1-5-07