Current through Register No. 50, December 12, 2024
Section Env-A 3308.03 - Processed Wood Residue Fuel QualityA large MWC facility combusting PWR shall only combust PWR that contains:
(a) No more than 1% by weight of non-wood materials, including but not limited to drywall, concrete, aggregates, dirt, and asbestos;(b) No more than 1.5% by weight of wood treated with creosote, pentachlorophenol, chromated copper arsenate, or other copper, chromium, or arsenical preservatives;(c) No more than 10% weight of #4 minus fines;(d) No more than a total of 50 parts per million (mg/kg) dry weight basis of arsenic; and(e) No more than a total of 250 parts per million (mg/kg) dry weight basis of lead.N.H. Admin. Code § Env-A 3308.03
Derived From Volume XXXVIII Number 41, Filed October 11, 2018, Proposed by #12628, Effective 9/27/2018, Expires 9/27/2028.