N.H. Admin. Code § Env-A 1305.14

Current through Register No. 50, December 12, 2024
Section Env-A 1305.14 - RACT Requirements: Boilers Firing Wood

For boilers that are subject to Env-A 1305.09(a) and fire wood fuel, or are capable of firing wood fuel, whether alone or in combination with oil, the NOx RACT requirements shall be as follows:

(a) For boilers equipped with a traveling, shaker, or vibrating grate, an emission limit of 0.33 lb. per million Btu, based on a 24-hour calendar day average; and
(b) For boilers equipped with a stationary grate, an emission limit of 0.25 lb. per million Btu, based on a 24-hour calendar day average.

N.H. Admin. Code § Env-A 1305.14

(See Revision Note at chapter heading for Env-A 1300) #9803, eff 10-31-10

Amended by Volume XXXVIII Number 32, Filed August 9, 2018, Proposed by #12584, Effective 8/15/2018, Expires 8/15/2028.