The NOx RACT requirements for dry-bottom industrial boilers that are subject to Env-A 1305.03(a) and fire, or are capable of firing, coal or oil, or any combination thereof, shall be as follows:
(a) For tangential-fired boilers, an emission limit of 0.38 lb. per million Btu, based on a 24-hour calendar day average;(b) For face-fired boilers, an emission limit of 0.50 lb. per million Btu, based on a 24-hour calendar day average; and(c) For stoker-fired boilers, an emission limit of 0.30 lb. per million Btu, based on a 24-hour calendar day average.N.H. Admin. Code § Env-A 1305.04
(See Revision Note at chapter heading for Env-A 1300) #9803, eff 10-31-10
Amended by Volume XXXVIII Number 32, Filed August 9, 2018, Proposed by #12584, Effective 8/15/2018, Expires 8/15/2028.