Current through November 8, 2024
Section 477.Sec. 2.3 - NEW1. A technician performing an inspection pursuant to NRS 477.093 shall: (a) Comply with the requirements of NRS 477.095;(b) Hold a certification issued in accordance with paragraph (b) of subsection 1 of NRS 477.093; and(c) Perform such inspection visually and in person regardless of the availability of remote testing capabilities or location.2. If the owner or operator of a building refuses a scheduled inspection, the technician must, not later than the end of the next business day after the date of the refusal, send a notice of refusal to the owner or operator of the building, the State Fire Marshal and the governing body.3. In addition to the requirements of subsection 2 of NRS 477.093, the owner or operator of any building equipped with a fire damper, smoke damper or combination fire and smoke damper shall maintain and make available for inspection, upon the request of the State Fire Marshal, a person authorized by the State Fire Marshal or a governing body, any inspection and testing documentation created during the three most recent inspections of the fire damper, smoke damper or combination fire and smoke damper.4. In addition to the requirements set forth in subsection 3 of NRS 477.095, a technician shall include in the certificate of inspection a description of any malfunctions or defects that were not fixed during the inspection of the fire damper, smoke damper or combination fire and smoke damper.5. As used in this section, "governing body" has the meaning ascribed to it in NRS 477.091.Nev. Admin. Code § 477.Sec. 2.3
Added to NAC by St. Fire Marshal by R048-24A, eff. 8/26/2024NRS 477.030, 477.093, 477.095