Nev. Admin. Code § 455.Sec. 4

Current through November 8, 2024
Section 455.Sec. 4 - NEW

A boiler must have a single, permanent means for disconnecting the boiler from all sources of electricity. The disconnecting means must be:

1. Of at least a general-duty type;
2. Capable of being locked in the open position;
3. Installed at an accessible location; and
4. An integral part of the boiler or located within 5 feet of the boiler.

Nev. Admin. Code § 455.Sec. 4

Added to NAC by Div. of Industrial Relations by R034-21A, eff. 7/26/2023

NRS 455C.110