Section 159-6-002 - OPERATION AND MAINTENANCE OF CATHODIC PROTECTION

The requirements of 40 CFR 280.31 as they existed on July 15, 2015 are adopted and incorporated by reference.

002.01A.Frequency. All cathodic protection systems must be tested within 6 months of installation; and
002.01A1. Impressed current cathodic protection systems will be tested annually thereafter; and
002.01A2. Galvanic or sacrificial anode cathodic protection systems will be tested at least every 3 years thereafter.