The following values may be entered in IECC Table 302.1 and used to determine compliance of subject buildings to be constructed anywhere in Nebraska:
Winter, Design Dry-bulb Temperature = -4°F
Summer, Design Dry-bulb Temperature = 92°F
Summer, Design Wet-bulb Temperature = 69°F
Degree days, heating (65° base) = 6500
Degree days, cooling (65° base) = 1000
Climate zone = 5
Interior Design Temperatures: Maximum of 72° (22° C) for heating and minimum of 75° (24°C) for cooling.
Use of these standard conditions for compliance determination does not relieve the designer of responsibility to size equipment correctly. The agency or designer may chose to use actual, historical weather data for the intended building site rather than these standard values.
103 Neb. Admin. Code, ch. 1, § 003