Mo. Code Regs. tit. 10 § 26-2.035

Current through Register Vol. 49, No. 23, December 2, 2024
Section 10 CSR 26-2.035 - Testing of Containment Sumps

PURPOSE: This rule contains the requirements for testing the newly required containment sumps associated with underground storage tank systems.

PUBLISHER'S NOTE: The secretary of state has determined that the publication of the entire text of the material which is incorporated by reference as a portion of this rule would be unduly cumbersome or expensive. This material as incorporated by reference in this rule shall be maintained by the agency at its headquarters and shall be made available to the public for inspection and copying at no more than the actual cost of reproduction. This note applies only to the reference material. The entire text of the rule is printed here.

(1) Owners and operators of underground storage tank (UST) systems with containment sumps required by 10 CSR 26-2.020 and/or 10 CSR 26-2.021, must ensure the continued integrity of required containment sumps by meeting one (1) of the following requirements:
(A) The containment sump has two (2) walls and the integrity of both walls is monitored annually; or
(B) The containment sump primary wall is tested at least triennially to ensure the equipment is liquid-tight by using vacuum, pressure, or liquid testing in accordance with one (1) of the following criteria:
1. Requirements developed by the manufacturer (Note: Owners and operators may use this option only if the manufacturer has developed testing requirements.);
2. An interstitial test or containment sump test listed by the National Work Group on Leak Detection Evaluations. To obtain copies of equipment certifications, contact the National Work Group for Leak Detection Evaluations, www.nwglde.org; or
3. Petroleum Equipment Institute RP 1200-12, Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities. This document is incorporated by reference without any later amendments or modifications. To obtain a copy, contact the Petroleum Equipment Institute, Box 2380, Tulsa, OK 74101-2380, (918) 494-9696, www.pei.org; or
4. Another method approved by department, including code(s) of practice developed by a nationally recognized association(s) or independent testing laboratory(ies), determined to be no less protective of human health and the environment than the requirements listed in paragraphs 1. through 3. of this subsection.
(2) Owners and operators must maintain record(s) of the required containment sump monitoring for twelve (12) months or test(s) required by this rule until the next test is performed.

10 CSR 26-2.035

Adopted by Missouri Register April 17, 2017/Volume 42, Number 08, effective 5/31/2017