When a change in elevation of the disposal trench is required, an additional distribution box or connecting lateral/crossover must be used. At the point where a crossover line leaves a lateral, the trench for the crossover line shall be dug no deeper than the top of the multi-pipe aggregate replacement distribution pipe in the preceding trench so that an undisturbed block of earth will remain in place for the full depth of the distribution system. Crossover lines shall be laid on undisturbed earth. The invert of the crossover must be at least four inches lower than the invert effluent line of the septic tank, aerobic treatment plant or vessel supplying effluent to the pipe.
15 Miss. Code. R. 18-77-5.5.13