Rule 15-10-76-3.2.11 - Steam Gauges
1. Each steam boiler shall have a steam gauge connected to its steam space, its water column, or its steam connection, by means of a siphon or equivalent device exterior to the boiler. The siphon shall be of sufficient capacity to keep the gauge tube filled with water and so arranged that the gauge cannot be shot off from the boiler except by a cock with a tee or lever handle placed in the pipe near the gauge. The handle of the cock shall be parallel to the pipe in which it is located when the cock is open.
2. The range of the scale on the dial of a steam boiler steam gauge shall be not less than 30 psi. The gauge shall be provided with effective stops for the indicating pointer at the zero point and at the maximum pressure point. The travel of the pointer from zero to full scale shall be at least three inches.