Subpart 1.Chapter 15.2.7.ANSI/IIAR 2, chapter 15.2.7, is amended to read as follows:
15.2.7. Relief valves shall not be located in refrigerated spaces unless precautions are taken to prevent moisture migration into the valve body or relief valve vent line. A drip pocket the size of the discharge pipe and at least 24 inches in length must be installed below a vertical riser in the discharge pipe and must be fitted with a drain plug or valve. Subp. 2.Chapter 15.2.8.2.ANSI/IIAR 2, chapter 15.2.8.2, is amended by adding the following paragraph at the end:
Rupture discs may only be used when installed in series with a pressure relief valve.
Subp. 3.Chapter 15.3.3.ANSI/IIAR 2, chapter 15.3.3, is amended by adding a subsection as follows:
15.3.3.1. Where the refrigerant inlet and outlet of air-cooled or evaporative condensers can be isolated, they shall be equipped with overpressure protection.Subp. 4.Chapter 15.4.3.ANSI/IIAR 2, chapter 15.4.3, is amended to read as follows:
11.3.3. The discharge piping from pressure relieving devices to atmosphere shall be a minimum schedule 40 steel for all pipe sizes.Minn. R. agency 206, ch. 5230, CODE FOR AMMONIA REFRIGERATION SYSTEMS, pt. 5230.5007