IFC section 1103.1 is amended to read:
Table 1103.1 is deleted.
IFC section 1103.2 is deleted.
IFC section 1103.3 is deleted.
IFC section 1103.4 is amended and sections added to read:
TABLE 1103.4
VERTICAL OPENING PROTECTION REQUIRED
OCCUPANCY CLASSIFI-CATION | CONDITIONS | PROTECTION REQUIRED |
Group I | Vertical openings connecting two or more stories | 1-hour protection |
All, other than Group I | Vertical openings connecting two stories | No protection requireda,b |
All, other than Group I | Vertical openings connecting three to five stories | 1-hour protection or automatic sprinklers throughouta,b |
All, other than Group I | Vertical openings connecting more than five stories | 1-hour protectiona,b |
All | Mezzanines open to the floor below | No protection requireda,b |
All, other than Group I | Atriums and covered mall buildings | 1-hour protection or automatic sprinklers throughout |
All, other than Groups B and M | Escalator openings connecting four or less stories in a sprinklered building. Openings must be protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. | No protection required |
Group B and M | Escalator openings in a sprinklered building protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. | No protection required |
a Vertical opening protection is not required for Group R-3 occupancies.
b Vertical opening protection is not required for open parking garages and ramps.
IFC subsections 1103.4.2, 1103.4.3, 1103.4.4, 1103.4.5, 1103.4.6, and 1103.4.7 are deleted.
IFC section 1103.5 is amended by adding new subsections to read:
Openings required by this section shall have a minimum dimension of 30 inches (762 mm).
If any portion of the basement is located more than 75 feet (22.86 m) from required openings, the basement shall be provided with an approved automatic sprinkler system throughout.
IFC section 1103.7 is deleted and replaced with the following:
In buildings containing mixed occupancies that are designed as separated uses (see Section 102.11), fire alarm and detection systems need only be installed in those occupancies where required by this section.
In areas protected by an approved, supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, automatic fire detectors required by Section 1103.7 need not be provided. Where Section 1103.7 requires smoke detectors, such protection shall be installed.
IFC section 1103.8 is amended and sections added to read:
TABLE 1103.8
SMOKE ALARM REQUIREMENTS
Condition: | Location: | Power Supply: | Interconnection Required: |
Existing buildings that do not have any smoke alarms (same as new). | In hallways outside sleeping rooms. In sleeping rooms. On each level of the building and in basements. On ceiling or wall (less than 12 inches below ceiling). On center of ceiling above stairways. | If constructed on or after 8/1/1989, smoke alarms are required to be hard-wired (120 volt). If constructed before 8/1/1989, smoke alarms can be battery-powered. | No interconnection is required for battery-powered alarms. |
Existing buildings (constructed on or after 8/1/1989). | In hallways outside sleeping rooms. On each level and in basements. On ceiling or wall (less than 12 inches below ceiling). | Smoke alarms are required to be hard-wired (120 volt). | No interconnection is required. |
Existing buildings (constructed before 8/1/1989). | In hallways outside sleeping rooms. On each level and in basements. On ceiling or wall (less than 12 inches below ceiling). | Smoke alarms can be battery-powered. | No interconnection is required. |
Replacement of smoke alarms in existing buildings. | Smoke alarms must be installed in same locations as originally installed. | Power supply must be the same as the smoke alarms being replaced. | Interconnection must be provided if the smoke alarms being replaced were interconnected. |
Smoke alarms shall be replaced with smoke alarms having the same type of power supply.
IFC section 1103.9 is deleted and replaced with the following:
Minn. R. agency 171, ch. 7511, pt. 7511.1103
Statutory Authority: MS s 326B.02