Part 1323.0680 - SECTION 6.8, MINIMUM EQUIPMENT EFFICIENCY TABLESSubpart 1.Table 6.8.2 Minimum duct insulation R-Value.ASHRAE 90.1 Table 6.8.2 is deleted and replaced with the following:
TABLE 6.8.2 Minimum Required Duct and Plenum Insulation
Ducts for Other Than Dwelling Units a,b | Supply Duct Requirements c,d | Return Duct Requirements c,d | Exhaust Duct and Relief Duct Requirements c,d,e,g |
Exterior of building | R-12, V and W | R-12, V and W | R-12, V and W |
Attics, garages, and ventilated crawl spaces | R-12 and V | R-12 and V | R-6 and V |
TD greater than 40°F | R-5 and V | None | R-5 and V |
TD greater than 15°F and less than or equal to 40°F | R-3.3 and V | None | R-3.3 and V |
Within concrete slab or within ground | R-3.5 and V | R-3.5 and V | None |
Within conditioned spaces | Nonef | None | None |
TD less than or equal to 15°F | None | None | None |
Ducts for Dwelling Unitsa | Requirementsc,d |
Exterior of building | R-12. V and W |
Attics, garages, and ventilated crawl spaces (except exhaust ducts) | R-12 and V |
Exhaust ducts in attics, garages, and ventilated crawl | |
spaces | R-3.3 and V |
Outdoor air intakes within conditioned spaces | R-3.3 and V |
Exhaust ducts within conditioned spacese | R-3.3 and V |
Within concrete slab or within ground | R-3.5 and V |
Within conditioned spaces | None |
°C=[(°F)-32]/1.8
a. Ducts located within the building thermal envelope shall be located completely on the conditioned side of the air barrierb. TD = Design temperature difference between the air in the duct and the ambient temperature outside of the duct, unless the duct type and location are specifically identified above. c. V = Vapor retarder required in accordance with Minnesota Rules, chapter 1346. When a vapor retarder is required, duct insulation required by this section shall be installed without respect to other building envelope insulation.d. W = Approved weatherproof barriere. Insulation is only required in the conditioned space for a distance of three feet (914 mm) from the exterior or unconditioned space. f. If the temperature rise is greater than 3°F from the supply air connection of the air handling unit to the furthest outlet, duct insulation shall be required for the entire length or for sufficient length to limit the temperature rise to 3°F.g. Insulation is not required on the exterior if low leak dampers are installed at roof or wall line or the exhaust is designed to be operated continuously.Subp. 2.ASHRAE 90.1 Table 6.8.3-1 Minimum piping insulation thickness heating and hot-water systems.ASHRAE 90.1 Table 6.8.3-1 is amended to add footnote "f" to read as follows:
f. Insulation requirements do not apply to those sections of piping used as the radiant heat source for radiant heating systems.Minn. R. agency 151, ch. 1323, pt. 1323.0680