Minn. R. agency 144, ch. 4725, WELL AND BORING GENERAL CONSTRUCTION AND USE REQUIREMENTS, pt. 4725.2550

Current through Register Vol. 49, No. 24, December 9, 2024
Part 4725.2550 - PLASTIC CASING AND COUPLING REQUIREMENTS
Subpart 1.General requirements.

Plastic casing and couplings used in the permanent construction of a well or boring must:

A. meet ASTM Standard F480-02, except that flush threaded polyvinyl chloride casing must not be used except for a monitoring well or environmental bore hole; and
B. withstand internal pressures of 200 pounds per square inch (psi).

Standard dimension ratios (SDR) and water pressure ratings (PR) at 23 degrees Celsius (73 degrees Fahrenheit) for nonthreaded polyvinyl chloride (PVC) and acrylonitrile-butadiene-styrene (ABS) plastic casing equal to or greater than 200 psi are as follows:

(1) pressure rating of PVC casing materials:

SDRPVC 1120PVC 1220PVC 2112PVC 2116PVC 2120
13.5315 psi315 psi200 psi250 psi315 psi
17250 psi250 psi-200 psi250 psi
21200 psi200 psi--200 psi

(2) pressure rating of ABS casing materials:

SDRABS 1316ABS 2112
13.5250 psi200 psi
17200 psi-

The sources of the pressure rating in item B are the American Society for Testing and Materials Standard D2241-04a "Standard Specifications for Poly(Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)" Table XI.I Standard Thermoplastic Pipe Dimension Ratios (SDR) and Water Pressure Rating (PR) at 73 degrees Fahrenheit (23 degrees Celsius) for Nonthreaded Plastic Pipe; and Standard D2282-99e "Standard Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe (SDR-PR)," Table XI.I Standard Plastic Pipe Dimension Ratios (SDR) and Water Pressure Ratings (PR) at 73 degrees Fahrenheit (23 degrees Celsius) for Nonthreaded ABS Plastic Pipe.

Subp. 2.Additional approved fittings and couplings.

In addition to the plastic couplings approved under subpart 1, the following fittings and couplings may be used to connect a steel pitless unit or screen to plastic casing:

A. fittings or couplings with socket dimensions meeting the requirements of ASTM Standard F480-02, Table 3 and having a water pressure rating of at least 200 psi;
B. Schedule 40, slip x internal thread fittings, four-inch and smaller meeting the requirements of ASTM D2466-02; or
C. Schedule 40, slip x internal thread fittings and slip x external thread fittings, five-inch diameter meeting the requirements of ASTM D2466-02.
Subp. 3.Compliance with ANSI/NSF standard required.

All plastic casings, couplings, components, and related joining materials including solvents, cements, or primers used in the construction of a well or boring must conform with the requirements of ANSI/NSF Standard 61-2003e or the health effects portion of ANSI/NSF Standard 14-2003 and be tested as conforming by an agency certified by the ANSI. Conformance to the ANSI/NSF standard must be coded, stamped, or marked on the casings, couplings, components, and related joining materials including solvents, cements, or primers.

Minn. R. agency 144, ch. 4725, WELL AND BORING GENERAL CONSTRUCTION AND USE REQUIREMENTS, pt. 4725.2550

17 SR 2773; 33 SR 211

Statutory Authority: MS s 103I.101; 103I.111; 103I.205; 103I.221; 103I.301; 103I.401; 103I.451; 103I.501; 103I.525; 103I.531; 103I.535; 103I.541; 103I.621; 144.05; 144.12; 144.383; 157.04; 157.08; 157.09; 157.13