The minimum isolation distances in item A or B must be maintained during construction, repair, or sealing of a well or boring, and installation of a pipe with flammable or volatile gas, an overhead or underground electric transmission, distribution, service, supply, feeder, branch, or conductor line hereafter called "electric line" or "line," or a liquid propane tank. The distances are measured horizontally from the closest part of the well or boring to the closest part of the pipe, tank, or line; or closest part of the vertical projection on the earth of an overhead or buried pipe, tank, or line. The minimum isolation distance between a well or boring and a pipe with flammable or volatile gas, an electric line, or a liquid propane tank is:
Subpart 1 does not apply to:
The requirements of this part are minimum standards and do not exempt persons from more restrictive requirements of the Occupational Safety and Health Administration.
Minn. R. agency 144, ch. 4725, WELL AND BORING GENERAL CONSTRUCTION AND USE REQUIREMENTS, pt. 4725.2150