Part 4725.5450 - VENTING WATER-SUPPLY WELLS
Subpart 1.Venting exceptions.

A water-supply well must be vented unless the well:

A. is a flowing well;
B. casing is used as a suction pipe;
C. has a packer jet assembly;
D. is used as a remedial well; or
E. is constructed with a watertight seal in lieu of a casing extension as specified in part 4725.4350, subpart 2.
Subp. 2.Vent construction.

A well vent must:

A. be constructed of materials complying with parts 4725.2250 to 4725.2650, or 4725.5150, subpart 1;
B. have watertight joints and terminate at least five feet above the regional flood level unless provided with a watertight seal as specified in part 4725.4350, subpart 2;
C. terminate a minimum of 12 inches above the established ground surface or the floor of a building as specified in part 4725.2175, except that a vent for a community public water-supply well must terminate a minimum of 18 inches above the established ground surface and the floor of a building as specified in part 4725.2175;
D. be screened with a noncorrosive mesh screen having openings of 1/16 inch or less and pointed downward; and
E. be connected to the casing according to part 4725.4850.
Subp. 3.Screened vents.

A screened vent incorporated into the underside of a well cap or cover may be used.

Subp. 4.Gas.

Any toxic or flammable gas must be vented from the well to the outside atmosphere.