Part 4725.5450 - VENTING WATER-SUPPLY WELLSSubpart 1.Venting exceptions.A water-supply well must be vented unless the well:
B. casing is used as a suction pipe;C. has a packer jet assembly;D. is used as a remedial well; orE. is constructed with a watertight seal in lieu of a casing extension as specified in part 4725.4350, subpart 2.Subp. 2.Vent construction.A well vent must:
A. be constructed of materials complying with parts 4725.2250 to 4725.2650, or 4725.5150, subpart 1;B. have watertight joints and terminate at least five feet above the regional flood level unless provided with a watertight seal as specified in part 4725.4350, subpart 2;C. terminate a minimum of 12 inches above the established ground surface or the floor of a building as specified in part 4725.2175, except that a vent for a community public water-supply well must terminate a minimum of 18 inches above the established ground surface and the floor of a building as specified in part 4725.2175;D. be screened with a noncorrosive mesh screen having openings of 1/16 inch or less and pointed downward; andE. be connected to the casing according to part 4725.4850.Subp. 3.Screened vents.A screened vent incorporated into the underside of a well cap or cover may be used.
Subp. 4.Gas.Any toxic or flammable gas must be vented from the well to the outside atmosphere.
Minn. R. agency 144, ch. 4725, WATER-SUPPLY WELLS, pt. 4725.5450