Minn. R. agency 105, ch. 1513, MINIMUM REQUIRED FLOW RATE OF PRESSURE RELIEF DEVICES FOR PROTECTION, pt. 1513.1100

Current through Register Vol. 49, No. 24, December 9, 2024
Part 1513.1100 - MINIMUM FLOW RATES

Pressure relief valves for excessive heat or fire protection used on containers covered by parts 1513.0300 to 1513.0380 and 1513.1000 to 1513.1070 must be constructed to discharge at not less than the rates required in this part before the pressure is in excess of 121 percent of the maximum allowable working pressure of the container. Relief protection for any other reason, except refrigerated storage, must use ASME UG-125 through UG-136.

Surface Area, Sq.Ft.Flow Rate, CFM AirSurface Area, Sq.Ft.Flow Rate, CFM AirSurface Area, Sq.Ft.Flow Rate, CFM Air
202581851,6009005,850
253101901,6409506,120
303601951,6701,0006,380
354082001,7101,0506,640
404552101,7801,1006,900
455012201,8501,1507,160
505472301,9201,2007,410
555912401,9801,2507,660
606352502,0501,3007,910
656782602,1201,3508,160
707202702,1801,4008,410
757622802,2501,4508,650
808042902,3201,5008,900
858453002,3801,5509,140
908853102,4501,6009,380
959253202,5101,6509,620
1009653302,5701,7009,860
1051,0103402,6401,75010,090
1101,0503502,7001,80010,330
1151,0903602,7601,85010,560
1201,1203702,8301,90010,800
1251,1603802,8901,95011,030
1301,2003902,9502,00011,260
1351,2404003,0102,05011,490
1401,2804503,3202,10011,720
1451,3105003,6202,15011,950
1501,3505503,9102,20012,180
1551,3906004,2002,25012,400
1601,4206504,4802,30012,630
1651,4607004,7602,35012,850
1701,5007505,0402,40013,080
1751,5308005,3002,45013,300
1801,5708505,5902,50013,520

Surface Area = Total Outside Surface Area of Container in Square Feet. If the surface area is not stamped on the nameplate or when the marking is not legible, the area can be calculated by using one of the following formulas:

(1)Cylindrical container with hemispherical heads Area = overall length in feet times outside diameter in feet times 3.1416.
(2)Cylindrical container with other than hemispherical heads Area = (overall length in feet plus 0.3 outside diameter in feet) times outside diameter in feet times 3.1416.
(3)Spherical container Area = outside diameter in feet squared times 3.1416.

Flow Rate--CFM Air = cubic feet per minute of air required at standard conditions, 60 degrees Fahrenheit and atmospheric pressure (14.7 psia).

The rate of discharge may be interpolated for intermediate values of surface area. For containers with total outside surface area greater than 2,500 square feet, the required flow rate can be calculated using the formula, Flow Rate CFM Air = 22.11 A0.82 where A = outside surface of the container in square feet.

CONVERSION FACTORS:
ft2x 0.092 903 = m2
CFMx 0.028 317 = m3/min
ftx 0.304 8 = m

Minn. R. agency 105, ch. 1513, MINIMUM REQUIRED FLOW RATE OF PRESSURE RELIEF DEVICES FOR PROTECTION, pt. 1513.1100

21 SR 277

Statutory Authority: MS s 18C.121