Rule 105. Sections 4-4 to 4-4.9.1, and table 4-4.9 of the storage and handling of gaseous and Liquefied H2 code are added as follows:
4-4 Special rooms.
4-4.1 Floors, walls, and ceiling shall be constructed of noncombustible or limited-combustible materials. Interior walls or partitions shall have a fire resistance rating of at least 2 hours, shall be continuous from floor to ceiling, and shall be securely anchored. At least 1 wall shall be an exterior wall. Windows and doors shall be located so as to be readily accessible in case of emergency.
Exception: Window glazing may be of plastic.
4-4.1.1 Access from within the primary structure shall be made through 1 vapor-sealing, 2 hour, self-closing fire door.
4-4.2 Ventilation shall be provided as in section 4-4.3.
4-4.3 Deflagration venting shall be provided in exterior walls or roof only.
4-4.3.1 Vents shall be any 1 or any combination of the following:
4-4.3.2 Where applicable, snow loads shall be considered.
4-4.3.3 The venting area shall be equal to not less than 1 cubic foot/30 cubic feet (1 cubic meter/9 cubic meters) of room volume.
4-4.4 There shall be no sources of ignition.
4-4.5 Electrical wiring and equipment shall comply with section 2-7, except that all electrical wiring and equipment in the special room shall be class I, division 2, group B.
4-4.6 Heating, if provided, shall be by steam, hot water, or other indirect means.
Exception: Electrical heating shall be in accordance with section 4-4.5.
4-4.7 Room ventilation.
4-4.7.1 The ventilation shall be at least 1 cubic foot/minute/square foot of room area, but not less than 1 cubic foot/minute/12 cubic feet of room volume and shall be designed such that an accumulation of H2 at a concentration equal to or greater than 25% of the lower flammable limit shall not occur in any part of the room.
4-4.7.2 Ventilation shall be by a continuous mechanical ventilation system or by a mechanical ventilation system activated by a continuously monitoring H2 detection system where a gas concentration of not more than 25% of the lower flammable limit is present.
4-4.7.3 Where installed, a gas detection system shall be equipped to sound an alarm and visually indicate when a maximum of 25% of the lower flammable limit is reached.
4-4.7.4 Any failure of the ventilation system shall immediately shut down the fueling system and provide notification to the system operator. Reactivation of the fueling system shall be by manual restart and shall be conducted by trained personnel.
4-4.7.5 The gas detection system shall function during ventilation system maintenance operations.
4-4.7.6 A ventilation system for a room within or attached to another building shall be designed to ensure that all areas serviced by the ventilation system meeting performance requirements in accordance with section 4-4.7 during the normal operating conditions and during alarm conditions.
4-4.8 Warning signs.
4-4.8.1 Access doors shall have warning signs with the words "WARNING - NO SMOKING - NONORDORIZED FLAMMABLE GAS - CRYOGENIC LIQUID -COLD GAS - NO OPEN FLAMES." The wording shall be in plainly legible, bright red letters not less than 1 inch (2.54 centimeters) high on a white background.
4-4.9 Indoor attended gaseous H2 fast-fill fueling.
4-4.9.1 Attended indoor fast-fill fueling system shall be in accordance with subsections (a) to (k) of this section.
Exemption: A dispensing area ventilation system is not required when the fuel delivery per refueling event is less than those listed in table 4-4.9.
Table 4-4.9
Room Size (m3) | Maximum fuel delivery per refueling event that does not require room ventilation (kg) |
1000 | 0. 8 |
2000 | 1.7 |
3000 | 2.5 |
4000 | 3.3 |
5000 | 4.2 |