Rule 101. Sections 3-5 to 3-5.2 of the storage and handling of gaseous and Liquefied H2 code are added as follows:
3-5 Installation of emergency shutdown equipment.
3-5.1 Breakaway protection shall be provided in a manner such that, if a pullaway event occurs, liquefied H2 will cease to flow at any separation.
3-5.2 A breakaway device shall be installed at every dispensing point. Such a device shall be arranged to separate by a force not greater than 150 pounds (75 kilograms), when applied in any direction that the vehicle would move. Breakaway devices shall be compatible with a standard acceptable to the department.
Mich. Admin. Code R. 29.7101