Mich. Admin. Code R. 29.1832

Current through Vol. 24-21, December 1, 2024
Section R. 29.1832 - Life safety code; new hospitals, mental hospitals, psychiatric hospitals, and psychiatric units; adoption by reference; amendment

Rule 32.

(1) The provisions of chapters 1 to 10, 11, 18, and 43 of the code that apply to new hospitals, new mental hospitals, new psychiatric hospitals, and new psychiatric units are adopted by reference in R 29.1802.
(2) Section 18.3.6.3.9.2 of the code is deleted and Section 18.4.3.7.2.1 of the code is amended to read as follows:
18.3.6.3.9.2 Deleted
18.4.3.7.2.1 Where the smoke compartment being modified is not protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.7, all of the following shall apply:
(1) Doors protecting corridor openings shall be constructed of 1-3/4 in. (44 mm) thick, solid-bonded core wood or of construction that resists the passage of fire for a minimum of 20 minutes.
(2) Door frames shall be labeled or of steel construction.
(3) Deleted.

Mich. Admin. Code R. 29.1832

2001 AACS; 2009 AACS; 2014 AACS