Rule 22. Sections 14.1.2.2, 14.1.6, 14.2.6.2, 14.2.6.3, 14.2.11.1.1, 14.2.11.2, 14.3.2.1, 14.3.4.1.2, 14.3.4.2.1, and 14.7.2.1 of the code are amended, sections 14.1.2.1.1, 14.1.2.2.1, 14.2.11.1.3, 14.3.2.5.1, 14.3.4.4, 14.3.4.5, 14.7.4.2.1, and 14.7.4.4 are added to the code, and sections 14.2.2.2.3.1, 14.3.4.2.3, 14.3.4.2.3.1, 14.3.4.2.3.2, 14.7.2.2, 14.7.2.3, and 14.7.3.3 are deleted to read as follows:
14.1.2.1.1. Educational occupancies shall include child care operations established and operated by an intermediate school board, the board of a local school district, the board or governing body of a state-approved nonpublic school, or by a person or entity with whom a school contracts for services, if the child care center is located in a school that is approved by the state fire marshal.
14.1.2.2. Unless otherwise permitted by section 14.1.2.1.1 educational occupancies shall not include any of the following:
14.1.2.2.1. A program specifically tailored for special needs children, special needs adults, or both, who range from 17 to 26 years of age, that is located in a community in a facility such as a shopping mall or business building, where the students will gain specific job experience and learn life studies, shall not be defined as a school.
14.1.6. For minimum construction requirements refer to the Michigan building code, R 408.30401 to R 408.30499.
14.2.2.2.3.1. Deleted.
14.2.6.2. Travel distances to an exit shall not exceed 200 feet (61 meters) from any point in a building, unless otherwise permitted by section 14.2.6.3.
14.2.6.3. Travel distance shall not exceed 250 feet (76.2 meters) in educational occupancies protected throughout by an approved automatic sprinkler system pursuant to Section 9.7.
14.2.11.1.1. The school or designated representative shall ensure every room or space which is more than 250 square feet (23.2 square meters) and which is used for classroom or other educational purposes or is normally subject to student occupancy shall have not less than 1 outside window for emergency rescue or ventilation that complies with the following unless otherwise permitted by section 14.2.11.1.2:
14.2.11.1.3. Windowless student occupied rooms in additions to existing buildings or renovated buildings shall be permitted where it is impractical to comply with section 14.2.11.1.1 where all of the following:
14.2.11.2. Lockups. Locking devices for designated "quiet rooms" shall meet all of the following criteria:
14.3.2.1. Rooms or spaces for the storage, processing, or use of materials specified in section 14.3.2.1(1) to (4) shall be protected pursuant to the following:
14.3.2.5.1. The school or designated representative shall ensure that any room that is used for instruction and has 3 or more gas outlets be provided with a master gas valve which shall be conveniently located outside the door of the room and be clearly marked so that the valve may be closed without having to enter the room. This section shall not apply to life skills rooms in which gas outlets supply stoves for cooking.
14.3.4.1.2. The requirement of section 14.3.4.1.1 shall not apply to a building meeting all of the following criteria:
14.3.4.2.1. Initiation of the required fire alarm system shall be by manual means pursuant to section 9.6.2.1(1). Manual fire alarm pull stations shall be provided pursuant to sections 9.6.2.2 to 9.6.2.5 of the code and at all exterior doors in the natural path of escape whether or not the path of escape is designated a required exit by these rules.
14.3.4.2.3. Deleted.
14.3.4.2.3.1. Deleted.
14.3.4.2.3.2. Deleted.
14.3.4.4. The school fire alarm system shall be provided with zone annunciation pursuant to the requirements of section 9.6.7 of the code.
14.3.4.5. In buildings provided with automatic extinguishing protective systems, all extinguishing system control valves shall be electronically supervised through the fire alarm system to cause an audible and visual supervisory signal at a location in the building where the signal will alert responsible personnel.
14.7.2.1. Emergency egress drills shall be conducted pursuant to the act.
14.7.2.2. Deleted.
14.7.2.3. Deleted.
14.7.3.3. Deleted.
14.7.4.2.1. Items permitted to be located in required egress corridors, provided the required clear width of the corridor is not obstructed, are limited to include fixed benches or hardwood or non-combustible material, trophy cases which are not used for excessive amounts of combustible materials, drinking fountains, telephones, vending machines, and other fixtures or items as approved by the authority having jurisdiction.
14.7.4.4. Desks and other instructional equipment shall be prohibited in required egress corridors.
Mich. Admin. Code R. 29.1922