Section R. 400.18635 - Fire doorsRule 635.
(1) A fire door shall bear the underwriters laboratories, incorporated, or factory mutual label, be installed in a labeled fire door frame, and be equipped with a self-closer and a latching device.(2) A fire door shall not be equipped with any hold-open device. A B-labeled fire door shall be provided as follows: (a) In an opening into a vertical shaft, such as any of the following:(i) A stairwell, rubbish, or incinerator shaft.(iii) A dumbwaiter shaft.(iv) A service shaft other than a ventilation duct opening.(b) In an opening into any of the following: (i) A storage room for ordinary combustible materials.(ii) A janitor room and closet.(iii) A linen room--both dirty and clean.(v) A heating plant room.(vi) A machine and fan room.(vii) A flammable liquid storage room.(ix) A laundry and rubbish bin room.(x) A laundry and rubbish chute feed room.(xii) A kitchen storage room.(xiii) An electrical service room.(c) An opening from a kitchen to required exit corridors in new construction.(d) Fire doors that are used in pairs without mullions shall be equipped with astragals and synchronizing closing devices. Astragals shall be made of not less than 10-gauge steel and shall be securely attached in place so as to project 3/4 of an inch.Mich. Admin. Code R. 400.18635