Section R. 400.14503 - Interior finishes and materials generally

Rule 503.

(1) Interior finish materials shall be at least class C materials throughout the adult foster care small group home.
(2) Interior finish materials shall be securely attached to, or furred out not more than 1 inch from, walls or ceilings that are dry wall, plaster, masonry, or natural solid wood that is not less than 3/4 of an inch thick.
(3) The attaching of interior finish materials, other than dry wall, plaster, or natural solid wood that is not less than 3/4 of an inch thick, directly to wall studs or to floor or ceiling joists is prohibited. Suspended ceilings constructed of a class A material that is 1/4 inch or greater in thickness and installed in accordance to manufacturers specifications shall be permitted.
(4) Class A, B, and C materials are interior finish materials that have the following minimum characteristics:

Class Flame Spread Smoke Developed

A 0-25 0-450

B 26-75 0-450

C 76-200 0-450