Mich. Admin. Code R. 408.40722

Current through Vol. 24-22, December 15, 2024
Section R. 408.40722 - Storage

Rule 722.

(1) An oxygen cylinder shall be stored not less than 20 feet from fuel gas cylinders or any highly combustible material, such as, but not limited to, oil, grease, excelsior, flammable gas, or a source of ignition, or shall be separated from the material by a noncombustible wall not less than 5 feet (1.6 meters) high which has a fire resistance rating of 30 minutes.
(2) A cylinder shall be stored away from any source of heat more than 125 degrees Fahrenheit.
(3) A cylinder, whether full or empty, in storage or during shipment, or with the regulator removed, shall have the valve closed and the cap connected in place if a cap is provided in the design, or shall be otherwise protected.
(4) Where different gases are stored, they shall be grouped by types. Groupings shall separate the fuel gases from the oxidizing gases as specified in subrule (1) of this rule.
(5) A storage area for cylinders shall be well ventilated.
(6) A cylinder shall not be stored in basements or pits.
(7) Where a liquid or gaseous oxygen system is used to supply gaseous oxygen for welding and cutting and the system has a storage capacity of more than 20,000 cubic feet (560 cubic meters), measured at 14.7 psia and 70 degrees Fahrenheit, including unconnected reserves at the site, the system shall be as prescribed in National Fire Protection Association Standard NFPA 50, "Standards for Bulk Oxygen Systems at Consumer Sites," 1974 edition, which is adopted by reference in R 408.40709.

Mich. Admin. Code R. 408.40722

1980 AACS; 2005 AACS; 2013 AACS; 2015 MR 4, Eff. March 3, 2015