Mich. Admin. Code R. 408.41867

Current through Vol. 24-22, December 15, 2024
Section R. 408.41867 - Dispensing

Rule 1867.

(1) An area where a flammable liquid is transferred at 1 time, in a quantity of more than 5 gallons from 1 tank or container to another tank or container, shall be separate from other operations or a building by a distance of 25 feet or by a wall not less than 5 feet high having a fire resistance of not less than 1 hour.
(2) Provisions shall be made to neutralize spills of flammable liquids. Natural or mechanical ventilation shall be capable of maintaining vapor below 10% of the lower explosive limit.
(3) Transfer of a category 1, 2, or 3 flammable liquid from 1 container to another shall be done only when the containers are electrically bonded.
(4) A flammable liquid shall be transferred from or drawn into containers by 1 of the following:
(a) Through a closed piping system.
(b) From a safety can.
(c) By a device drawing through the top from a closed container or portable tank, by gravity or a pump, through a self-closing valve. Air pressure shall not be used.
(5) A dispensing device, hose, and nozzle for category 1, 2, or 3 flammable liquids shall be an approved type.
(6) The dispensing units shall be protected from collision damage.

Mich. Admin. Code R. 408.41867

1979 AC; 1983 AACS; 2015 MR 7, Eff. April 14, 2015