Section R. 408.41867 - DispensingRule 1867.
(1) An area where a flammable liquid is transferred at 1 time, in a quantity of more than 5 gallons from 1 tank or container to another tank or container, shall be separate from other operations or a building by a distance of 25 feet or by a wall not less than 5 feet high having a fire resistance of not less than 1 hour.(2) Provisions shall be made to neutralize spills of flammable liquids. Natural or mechanical ventilation shall be capable of maintaining vapor below 10% of the lower explosive limit.(3) Transfer of a category 1, 2, or 3 flammable liquid from 1 container to another shall be done only when the containers are electrically bonded.(4) A flammable liquid shall be transferred from or drawn into containers by 1 of the following: (a) Through a closed piping system.(c) By a device drawing through the top from a closed container or portable tank, by gravity or a pump, through a self-closing valve. Air pressure shall not be used.(5) A dispensing device, hose, and nozzle for category 1, 2, or 3 flammable liquids shall be an approved type.(6) The dispensing units shall be protected from collision damage.Mich. Admin. Code R. 408.41867