Current through Vol. 24-21, December 1, 2024
Section R. 325.10705 - Collection and analysis of samples for coliform bacteria; community water systemsRule 705.
(1) A supplier of water of a community water system shall collect samples of water to be analyzed for the presence of coliform bacteria at sites which are representative of water throughout the distribution system according to a written sample siting plan that is subject to department review and revision.(2) The monitoring frequency for total coliforms for a community water system is based on the population served by the system as set forth in table 1 of this rule: Table 1 Total Coliform Monitoring Frequency for Community Water Supplies
Population Served | Minimum Number of Samples Per Month |
25 to 1,000 * | 1 |
1,001 to 2,500 | 2 |
2,501 to 3,300 | 3 |
3,301 to 4,100 | 4 |
4,101 to 4,900 | 5 |
4,901 to 5,800 | 6 |
5,801 to 6,700 | 7 |
6,701 to 7,600 | 8 |
7,601 to 8,500 | 9 |
8,501 to 12,900 | 10 |
12,901 to 17,200 | 15 |
17,201 to 21,500 | 20 |
21,501 to 25,000 | 25 |
25,001 to 33,000 | 30 |
33,001 to 41,000 | 40 |
41,001 to 50,000 | 50 |
50,001 to 59,000 | 60 |
59,001 to 70,000 | 70 |
70,001 to 83,000 | 80 |
83,001 to 96,000 | 90 |
96,001 to 130,000 | 100 |
130,001 to 220,000 | 120 |
220,001 to 320,000 | 150 |
320,001 to 450,000 | 180 |
450,001 to 600,000 | 210 |
600,001 to 780,000 | 240 |
780,001 to 970,000 | 270 |
970,001 to 1,230,000 | 300 |
1,230,001 to 1,520,000 | 330 |
1,520,001 to 1,850,000 | 360 |
1,850,001 to 2,270,000 | 390 |
2,270,001 to 3,020,000 | 420 |
3,020,001 to 3,960,000 | 450 |
3,960,001 or more | 480 |
* Includes public water supplies which have not less than 15 service connections, but which serve fewer than 25 persons.
(3) If a community water system that serves 25 to 1,000 persons does not have a history of total coliform contamination in its current configuration and a sanitary survey conducted in the past 5 years shows that the system is supplied solely by a protected groundwater source and is free of sanitary defects, the department may reduce the monitoring frequency specified in table 1 of this rule, except that the department shall not reduce the monitoring frequency to less than 1 sample per quarter. To be valid, the reduced monitoring frequency shall be approved, in writing, by the department.(4) Suppliers of water for all community water systems and noncommunity water systems shall collect samples at regular time intervals throughout the monitoring period, except for those groundwater supplies which serve fewer than 4,901 persons and which are not influenced by surface water. Groundwater suppliers that serve fewer than 4,901 persons may collect all required samples on a single day if the samples are taken from different sites.Mich. Admin. Code R. 325.10705
1979 AC; 1991 AACS; 1993 AACS; 2002 AACS