Current through Register Vol. 51, No. 22, November 1, 2024
Section 26.10.18.04 - Performance Standards for a Field-Erected AST SystemAn owner, an operator, and a person in charge of an AST system with a field-erected AST shall:
A. Ensure the field-erected AST is: (1) Properly designed for the oil storage application and type of oil to be stored;(2) Constructed of welded carbon steel or stainless steel; and(3) Constructed to an industry standard, including an API standard for field-erected ASTs incorporated by reference in COMAR 26.10.01.03;B. Ensure the foundation of the field-erected AST: (1) Is designed and constructed in accordance with Annexes B and I of API Standard 650 "Welded Tanks for Oil Storage" to prevent settlement of the foundation and the AST due to soil bearing capacity and other site conditions using: (a) Field and laboratory testing; and(b) Analyses and other sound engineering practices performed by a professional engineer;(2) Is capable of supporting the load of the AST and its contents without excessive differential settlement; and(3) Provides positive drainage of water away from the AST base; andC. Test a new, repaired, or relocated AST system for tightness in accordance with NFPA 30 "Flammable and Combustible Liquids Code":(1) Upon completion of the installation or repair of the AST system; and(2) Before placing the AST system in-serviceMd. Code Regs. 26.10.18.04
Regulation .04 adopted effective 49:12 Md. R. 642, eff. 6/13/2022