Section 26.10.17.05 - Performance Standards for AST Systems with a Shop-Fabricated ASTAn owner, an operator, and a person in charge of an AST system with a shop-fabricated AST shall:
A. Ensure the AST system is: (1) Properly selected for the oil storage application and type of oil stored; and(2) Constructed to an industry standard, including a UL, STI or API standard;B. Ensure the foundation for a stationary shop-fabricated AST is:(1) Constructed to: (b) Prevent movement and uneven settlement of the foundation and the AST; and(c) Provide positive drainage of water away from the foundation;(2) Capable of supporting the soil-bearing pressure of the AST and its contents; and(3) Designed by a qualified professional engineer using field and laboratory testing and analyses, if the AST system is located in an area subject to flooding;C. Install an elevated AST system, unless: (1) An alternate AST system is approved by the Department in writing; and(2) The owner, the operator, and the person in charge of the alternate AST system installs, tests, and maintains a cathodic protection system in accordance with Regulation .10 of this chapter; andD. Test a new, repaired, or relocated AST system for tightness in accordance with NFPA 30 "Flammable and Combustible Liquids Code":(1) Upon completing the installation or repair of the AST system; and(2) Before placing the AST system in-service.Md. Code Regs. 26.10.17.05
Regulation .05 adopted effective 49:12 Md. R. 642, eff. 6/13/2022