Section 10.17.01.23 - Equipment RoomsAn owner shall ensure that a recreational pool, semipublic pool, or public spa has an equipment room that:
A. Houses the pool or spa circulation, filtration, and disinfection equipment; andB. Has:(1) Weathertight construction to prevent the entrance of precipitation;(2) Adequate floor area for safe access to all equipment;(3) A minimum ceiling height of 7 feet 6 inches;(4) A waterproof floor that drains to a floor drain;(5) A lockable entrance door that allows complete and unencumbered access to the equipment room;(6) A minimum of 20 footcandles of artificial illumination;(7) Ventilation sized at 2 cubic feet per minute per square foot of floor area that is: (a) Mechanical exhaust ventilation if chemicals are used or stored in the equipment room, or(b) Natural or mechanical exhaust ventilation if chemicals are not used or stored in the equipment room;(8) Adequate make-up air to replace the air exhausted by the ventilation system;(9) A hose bibb with an atmospheric vacuum breaker; and(10) A water-resistant data sheet that is posted in a conspicuous place for each pool or spa and that includes the following information:(b) Minimum turnover rate,(c) Maximum filter capacity,(e) Length of water perimeter,(f) Maximum bather load, and(g) Operating instructions for valves and equipment.Md. Code Regs. 10.17.01.23