(TS x t x E)/(R x FS) = maximum allowable working pressure, PSIG, where:
Single lap weld ... 40 percent
Double lap weld ... 60 percent
Single butt weld ... 60 percent
Double butt weld ... 75 percent
Forge weld ... 70 percent
Brazed steel ... 80 percent
Md. Code Regs. 09.12.01.26
Regulation .26B amended effective July 3, 1995 (22:13 Md. R. 966)