Section 09.12.01.07 - Gas-Fired InstallationsA. A burner in a gas-fired installation shall be tested and certified by the American Gas Association.B. A gas-fired boiler shall have a vent or flue that terminates at an acceptable location outside the building.C. The size of the vent or flue shall be: (1) That recommended by the boiler manufacturer;(2) At least 4 inches in diameter or equivalent area; and(3) If the horizontal run exceeds 10 feet, at least 6 inches in diameter or equivalent area.Md. Code Regs. 09.12.01.07