C.M.R. 16, 219, ch. 34, app 219-34-B

Current through 2024-51, December 18, 2024
Appendix 219-34-B

Table 4.3.2.4 State of Maine Minimum Separation Requirements for Aboveground Tanks
Tank TypeIndividual Tank Capacity (gal) (See 4.3.2.3 and 4.3.2.5) Minimum distance from the nearest important building on the same property (ft) Minimum distance from the nearest fuel dispensing device (ft) (see 4.3.2.6)Minimum distance from lot line that is or can be built upon, including the opposite side of a public way (ft)Distance from the nearest side of any public way (ft)Minimum distance between tanks (ft)
Tanks in Vaults* 0 - 12,00025255025Separate compartments required for each tank
Protected aboveground tanks less than or equal to 6,000 501553
6,001 - 12,000 152525153
Fire resistant tanks 0 - 12,000252550253
Other tanks meeting the requirements of NFPA 30A 0 - 12,0005050100503

C.M.R. 16, 219, ch. 34, app 219-34-B