02-658-205 Me. Code R. § 2

Current through 2024-51, December 18, 2024
Section 658-205-2 - LOW WATER CONTROL FOR HOT WATER BOILERS
1. All hot water boilers installed or converted after January 1, 1999, must be provided with a low-water cut off.

Exception: This requirement pertains to the installation of the pressure vessel only. All boilers, whether steam or hot water, installed after January 1, 1999, must be protected by a low-water cut off. Steam boilers, regardless of installation date, are required to be protected with a low-water cut off.

2. The low-water cut off may be installed in or attached to the boiler at the level recommended by the boiler manufacturer, but in no case shall the low-water cut off be installed below the crown sheet. The low-water cut off, when not installed directly in the boiler, may be installed either in the main supply line (Vertical riser) as close to the boiler as possible, or in a water column of continuous piping attached directly to the boiler.
3. The low-water cut off must be designed and approved for the medium used (steam or water).
4. No valves or other obstructive devices shall be installed between the boiler and safety controls.

02-658 C.M.R. ch. 205, § 2