02-658-14 Me. Code R. § 5

Current through 2024-51, December 18, 2024
Section 658-14-5 - Container Installation Under Decks or Other Structures

Cylinders and ASME containers of 125 gallons water capacity or less may be located and installed underneath a deck or other structure, provided all of the following conditions are met:

1. The space is completely open to the atmosphere for 50 percent of its perimeter or more;
2. There is a minimum of two (2) feet vertical clearance between the top of the tank and any part of the structure;
3. The maximum aggregate water capacity of such tanks is no more than 250 gallons; and
4. The container is not installed beneath a means of egress, as defined by the local Authority Having Jurisdiction.

02-658 C.M.R. ch. 14, § 5