Water-riser pipes shall be a minimum of 3/4 in. nominal diameter.Water-riser pipes shall extend a minimum of 6 in. above ground elevation.Water riser pipes shall be terminated with a threaded plug, hose bib, or cap when a manufactured home does not occupy a site.Surface drainage shall be diverted from the location of the riser pipe.
An accessible shutoff valve shall be provided on the water-riser pipe serving the manufactured home.The system shall be protected from backflow for single family residences on shared wells.
Provision shall be made to protect the water supply piping and valves, including the riser.
A well shall not be located within the boundaries of a manufactured homepad.
02-385 C.M.R. ch. 900, § C-II